Electrical Energy Calculator
Calculate electricity use from power and duration, or constant DC voltage and current. Compare energy use over different operating times in watt-hours, kilowatt-hours and joules.
Open toolInteractive calculation is unavailable until JavaScript loads. The formulas and reference information below remain available.
Calculate balanced three-phase real, reactive and apparent power and convert line and phase voltage or current for wye (star) or delta connections.
Choose Wye (star) or Delta.
Enter one voltage, say whether it is line-to-line or phase, and choose its unit.
Enter one current, say whether it is a line or phase current, and choose its unit.
Enter the power factor or drag its slider, and choose Lagging or Leading.
Read total real power, then apparent and reactive power and the line and phase values. The diagram shows where each value is measured.
Open Show the steps for the substituted formulas. Copy result copies every value. Reset restores the starting values.
A three-phase supply has three voltages of equal size, 120° apart. Line-to-line voltage is measured between two supply conductors; phase voltage is across one load branch.
In a wye (star) connection each branch sits between a line and the neutral point, so the branch carries the line current, and the line-to-line voltage is √3 times the phase voltage, because two phase voltages 120° apart add to √3 times either one.
In a delta connection each branch sits between two lines, so the branch voltage equals the line voltage, and each line current is √3 times a branch current.
Either way, total apparent power is √3 × V_L × I_L, which equals 3 × V_ph × I_ph. Real power is apparent power times the power factor, and reactive power follows from S² = P² + Q².
Limitations: the calculation assumes a balanced load with sinusoidal voltages and currents. Unbalanced loads, harmonics, motor efficiency and starting current are not included. Nameplate motor power is output power; input power is higher by the motor's efficiency.
Wye: V_L = √3 × V_ph and I_L = I_ph. V_L is line-to-line voltage, V_ph phase (line-to-neutral) voltage, I_L line current, I_ph branch current.
Delta: V_L = V_ph and I_L = √3 × I_ph.
Apparent power: S = √3 × V_L × I_L = 3 × V_ph × I_ph, in VA.
Real power: P = S × PF, in W; per phase P ÷ 3.
Reactive power: Q = ±S × √(1 − PF²), in var; + for lagging (inductive), − for leading (capacitive).
Wye, 400 V line-to-line, 10 A line current, PF 0.8 lagging: P 5.543 kW, S 6.928 kVA, Q 4.157 kvar, phase voltage 230.9 V. S = √3 × 400 × 10; the phase voltage is 400 ÷ √3.
Delta, 480 V, 20 A line current, PF 0.85 lagging: P 14.13 kW, phase current 11.55 A. In delta the branch current is the line current divided by √3.
Wye, 230 V phase voltage, 10 A, PF 1: Line voltage 398.4 V, P 6.9 kW. Common mistake: using 230 V with √3 gives 3.984 kW, too low by √3. Use V_L with √3, or V_ph with 3.
All About Circuits: Three-phase Y and delta configurations
Available now
Calculate electricity use from power and duration, or constant DC voltage and current. Compare energy use over different operating times in watt-hours, kilowatt-hours and joules.
Open tool →Available now
Add up to 20 resistors in series using Ω, kΩ or MΩ for circuit analysis and electricity calculations, with a diagram and running total.
Open tool →Available now
Convert absolute temperatures between Celsius, Fahrenheit and kelvin.
Open tool →Nice audio board working as expected.
Given the fact that this was my first purchase and I made it thinking I was buying genuine Yihua products, this has been a setback. I received a lesser known OEM brand called MYTO and while both the products seem to be similar from appearance, my real contention is the quality and quantity of the brass wool. On top of that not informing the customer about the unavailability of the Yihua product and instead sending a product from a different brand is also antagonising. Henceforth, I might just have to think twice before ordering from ThinkRobotics.
TOF MINIF Range Sensor - UART TOF Time-of-Flight Laser Range Sensor
We are disappointed with our recent order experience. We clearly communicated our requirement for 433 MHz antennas on WhatsApp, but the issue remains unresolved. We have been following up for more than 10 days and are still waiting for a proper refund resolution.
As a regular B2B customer, we expected better support. This experience has affected our trust in ThinkRobotics, and we may have to consider other suppliers for future purchases. We request a fair and prompt refund.
Anodised Aluminium Cup Head Washers (Pack of 10)