Three-phase delta/wye power calculator

Enter RMS values. Line values are measured between supply conductors; phase values across one load branch.

No valid result to draw.

Show the steps

Interactive calculation is unavailable until JavaScript loads. The formulas and reference information below remain available.

Calculate balanced three-phase real, reactive and apparent power and convert line and phase voltage or current for wye (star) or delta connections.

How to use

Choose Wye (star) or Delta.

Enter one voltage, say whether it is line-to-line or phase, and choose its unit.

Enter one current, say whether it is a line or phase current, and choose its unit.

Enter the power factor or drag its slider, and choose Lagging or Leading.

Read total real power, then apparent and reactive power and the line and phase values. The diagram shows where each value is measured.

Open Show the steps for the substituted formulas. Copy result copies every value. Reset restores the starting values.

Science

A three-phase supply has three voltages of equal size, 120° apart. Line-to-line voltage is measured between two supply conductors; phase voltage is across one load branch.

In a wye (star) connection each branch sits between a line and the neutral point, so the branch carries the line current, and the line-to-line voltage is √3 times the phase voltage, because two phase voltages 120° apart add to √3 times either one.

In a delta connection each branch sits between two lines, so the branch voltage equals the line voltage, and each line current is √3 times a branch current.

Either way, total apparent power is √3 × V_L × I_L, which equals 3 × V_ph × I_ph. Real power is apparent power times the power factor, and reactive power follows from S² = P² + Q².

Limitations: the calculation assumes a balanced load with sinusoidal voltages and currents. Unbalanced loads, harmonics, motor efficiency and starting current are not included. Nameplate motor power is output power; input power is higher by the motor's efficiency.

Formulas

Wye: V_L = √3 × V_ph and I_L = I_ph. V_L is line-to-line voltage, V_ph phase (line-to-neutral) voltage, I_L line current, I_ph branch current.

Delta: V_L = V_ph and I_L = √3 × I_ph.

Apparent power: S = √3 × V_L × I_L = 3 × V_ph × I_ph, in VA.

Real power: P = S × PF, in W; per phase P ÷ 3.

Reactive power: Q = ±S × √(1 − PF²), in var; + for lagging (inductive), − for leading (capacitive).

Examples

Wye, 400 V line-to-line, 10 A line current, PF 0.8 lagging: P 5.543 kW, S 6.928 kVA, Q 4.157 kvar, phase voltage 230.9 V. S = √3 × 400 × 10; the phase voltage is 400 ÷ √3.

Delta, 480 V, 20 A line current, PF 0.85 lagging: P 14.13 kW, phase current 11.55 A. In delta the branch current is the line current divided by √3.

Wye, 230 V phase voltage, 10 A, PF 1: Line voltage 398.4 V, P 6.9 kW. Common mistake: using 230 V with √3 gives 3.984 kW, too low by √3. Use V_L with √3, or V_ph with 3.