UPS/inverter energy-runtime estimator

Enter the AC load the inverter supplies; the battery also pays for the inverter's losses.

Two 12 V batteries in series make a 24 V bank.

Inverter

From the data sheet; Victron lists 84 to 96% maximum efficiency for its 250 W to 5 kVA inverters.

The data sheet's zero-load or no-load power, for example 5 to 20 W.

Rate effect (Peukert)

1 turns the rate effect off. Victron's default for lead acid is 1.25; use the battery's data sheet value if it has one.

The hours behind the capacity rating, for example 20 for a C20 rating.

Enter the battery, the AC load and the inverter efficiency to see the runtime.

No energy split to draw.

Show the steps

Interactive calculation is unavailable until JavaScript loads. The formulas, worked examples and references below remain available.

Estimate UPS or inverter backup runtime from battery energy, AC load, inverter efficiency, idle power and usable capacity, or the battery energy needed for a target runtime.

How to use

Choose Backup runtime, or Battery for a target runtime.

Enter the bank's capacity in Ah or Wh (for runtime) and its nominal voltage.

Enter the AC load in watts, or in VA with its power factor.

Enter the inverter efficiency and, if you know it, the idle power from the data sheet; set the usable capacity.

For lead-acid banks under heavy loads, open Rate effect (Peukert) and enter the exponent and the rated discharge time.

Read the runtime or the battery needed, the DC current and the energy bar. Copy result copies labelled values; Reset clears the values and restores the starting choices.

Science

A UPS or inverter turns the battery's DC energy into AC power. The battery has to supply the load plus the inverter's losses, so the power it delivers is the load divided by the efficiency, plus whatever the inverter draws just to stay on.

A battery bank's energy in watt-hours is its ampere-hours times its nominal voltage, and it is the same whether its batteries are wired in series or in parallel. Dividing the usable energy by the battery-side power gives the runtime; dividing the battery-side power by the bank voltage gives the DC current the cables and fuse must carry.

Watts are not volt-amperes. An AC load's real power is its volt-amperes times its power factor, and only real power drains the battery, so a "1000 VA" UPS at a power factor of 0.6 supplies at most 600 W.

Batteries, especially lead-acid, deliver less than their rated capacity when discharged quickly. Peukert's law describes this with an exponent: 1 means no effect, and Victron uses 1.25 as a typical lead-acid value. At a load that would empty the battery in well under its rated hours, the runtime falls much faster than the energy alone suggests.

Limitations: efficiency and idle power are held constant, although real inverters are less efficient at light load and a data sheet's peak efficiency may already include the idle draw. Battery voltage sag, temperature, ageing, the UPS's low-voltage cut-off and surge loads are not modelled, and Peukert's law is only a rough fit. Treat the result as an estimate and test the real system.

Formulas

Battery power: P_b = P_L / η + P_0. P_L is the AC load in watts, η the inverter efficiency, P_0 the idle power.

Real load from VA: P_L = S × pf, where S is in VA and pf is the power factor.

Runtime: t = u × E / P_b, with E = Q × V the bank energy in Wh and u the usable fraction.

Rate effect: t = u × H × (E / (P_b × H))^k, for loads heavier than the H-hour rate.

DC current: I_dc = P_b / V.

Battery for a target: E = P_b × t₀, with t₀ = H × (t / (u × H))^(1/k) for heavy loads, or t / u otherwise.

Examples

12 V 100 Ah, 500 W load, 90% efficient: 2 h 10 min (2.16 h). 1,200 Wh ÷ 555.6 W; the battery supplies 46.3 A.

Same, inverter idle power 8 W: 2 h 8 min (2.129 h). 563.6 W from the battery; the idle draw uses 17 Wh.

800 VA load at power factor 0.6, 90% efficient, 8 W idle, 80% usable, 1,200 Wh: 1 h 46 min. 800 VA × 0.6 = 480 W of real load.

UPS with two 12 V 9 Ah batteries in series, 300 W, 85% efficient: 36 min 43 s without the rate effect; 15 min 21 s with Peukert 1.25 at C20. The 216 Wh bank would empty in 0.612 h, far faster than its 20 h rating.

Battery for 1 hour of 500 W at 90%, 12 V: 555.6 Wh, 46.3 Ah. With Peukert 1.25 at C20 the same hour needs 1,011 Wh (84.29 Ah).

Common mistake: 1000 VA UPS treated as 1000 W: A 600 W real load at power factor 0.6. Use the watt rating, or VA times the power factor.

References

OpenStax University Physics Volume 2, 15.4 Power in an AC Circuit

OpenStax College Physics 2e, 7.6 Conservation of Energy (Efficiency)

OpenStax University Physics Volume 2, 9.5 Electrical Energy and Power

Victron Energy BMV-712 Smart manual: Battery capacity and Peukert exponent

Victron Energy Inverter Smart 1600 VA – 5000 VA data sheet

Victron Energy Inverter VE.Direct 250 W – 1600 W 230 V data sheet

Sandia SAND2007-5036: Performance Model for Grid-Connected Photovoltaic Inverters

MIT Electric Vehicle Team: A Guide to Understanding Battery Specifications