CRZ OAC15 AC Output Module - 3A, 12 ~ 140VAC Output

The CRZ OAC15 is a high-performance solid state I/O output module manufactured by SENSATA/CRYDOM. Designed for demanding industrial environments, this module provides reliable switching of AC loads with zero cross switching technology, ensuring noise-free operation and long-term durability.

  • Part Number: OAC15
  • Manufacturer: SENSATA/CRYDOM
  • Country of Origin: MX
  • Unit of Measure: EA
  • ECCN: EAR99
  • Package Type: Not specified
  • Datasheet: Download Datasheet

Product Features

  • AC output capable of switching loads up to 3A
  • Operating voltage range: 12 to 140 VAC
  • Zero cross switching for reduced electrical noise and prolonged device life
  • Status indicating LED for operational status monitoring
  • UL, CSA, and CE approved for safety and compliance
  • Solid state design ensures high reliability and long service life

Technical Specifications

Parameter Details
Input Voltage Nominal 12 ~ 140 VAC
Output Current 3A
Max Line Voltage 140 VAC
Min Line Voltage 12 VAC
Peak Off-State Voltage 400 V peak
Max On-State Current 3A
Max Surge Current 100A peak per cycle
Operating Temperature Range -30°C to +80°C
Isolation Voltage 4,000 Vrms

Additional Information

This AC output module is suitable for controlling motors, valves, solenoids, and other AC loads. It features a fast turn-on and turn-off time of approximately half a cycle, ensuring precise control. The module also includes a fuse rating of 4A (fast-acting) for X4 series models.

For detailed application notes and wiring diagrams, please refer to the datasheet.

Note: Do not install or remove modules in live circuits. An externally located commutating diode must be installed across inductive loads.