Industrial Relays 240VAC 1PH 3PH Load Guard 5A - CG (Part Number: DWA01CM235A)

Enhance your electrical system's reliability with the CARLO GAVAZZI Industrial Load Guard Relays, designed for monitoring 3-phase loads and motor performance. These relays are ideal for applications requiring precise cos φ monitoring, overload, and underload detection, ensuring optimal operation and protection of your electrical equipment.

Product Features

  • Type: Monitoring relays with 3-phase load guard functionality
  • Voltage Range: 240VAC (Power Supply: 208-240 VAC)
  • Current Measurement: 5A standard, compatible with MI current transformers
  • Output: 8 A SPDT relay, Normally Energized
  • Housing Options: 22.5 mm Euronorm DIN-rail mounting (DWA01) or 36 mm plug-in module (PWA01)
  • Adjustable Power ON delay: 1, 2, or 6 seconds
  • Knob adjustable level on an absolute scale from 0.1 to 0.99 for cos φ monitoring
  • LED Indicators: Power supply status and output ON
  • Mounting: DIN-rail or plug-in module in accordance with DIN/EN 50 022
  • Monitoring Capabilities: Measures voltage, current, and power factor (cos ϕ) for balanced systems
  • Application: Suitable for asynchronous motor load monitoring, overload, and underload detection

Technical Specifications

Parameter Details
Part Number DWA01CM235A
Manufacturer CARLO GAVAZZI
Country of Origin Italy (IT)
UOM EA
ECCN EAR99
Package Type DIN-rail or Plug-in Module
Datasheet Download Datasheet

Application and Operation

The DWA01 and PWA01 relays are designed for monitoring the actual load of asynchronous motors by measuring the 3-phase supply voltage and the current of phase L1. They monitor the cosine of the phase angle (cos ϕ), which varies with motor load, allowing indirect detection of overload or underload conditions.

Overload monitoring: The relay operates and the yellow LED indicates status when cos ϕ drops below the set limit. It releases when the limit is exceeded.

Underload monitoring: The relay operates and the yellow LED indicates status when cos ϕ exceeds the set limit. It releases when the load drops below the set threshold.

The relays feature an inhibit delay at power-on to prevent false alarms during motor startup, ensuring reliable operation.

Dimensions

Note

Specifications are subject to change without notice. For more detailed information, please refer to the datasheet or contact the manufacturer.

For additional details, visit the product datasheet.


Our team will contact you with bulk pricing!

Want to buy in bulk?

Meet with our team

Custom Requirements?

Discussion Forum

Welcome to the discussion thread for DWA01CM235A
Feel free to ask questions, share tips or report issues.